20kWh–60kWh High-Voltage Rack-Mounted LiFePO4 Battery System
Rack-Mounted LiFePO4 Batteries

20kWh–60kWh High-Voltage Rack-Mounted LiFePO4 Battery System

Chudu Metal 20kWh–60kWh High-Voltage Rack-Mounted LiFePO4 Battery System for Solar Energy Storage

    d12d6731-f9f7-479e-9b62-2b8ac2ce1712
    d6cc8cf1-f2ec-4afe-93a2-b7dafd93682e
    226c8e2d-cfcb-40c8-baa0-b447260c3941

    Product Overview


    Chudu Metal 20kWh–60kWh High-Voltage Rack-Mounted LiFePO4 Battery Systems are designed for residential, commercial, off-grid and backup energy storage applications requiring higher battery voltage and modular capacity expansion.

    The system uses Lithium Iron Phosphate (LiFePO4 / LFP) battery modules installed in a rack or battery cabinet. Multiple 51.2V battery modules are connected in series to form a high-voltage battery cluster.

    Typical system capacities range from approximately 20.48kWh to 61.44kWh, with nominal system voltage from approximately 204.8VDC to 614.4VDC, depending on the number of battery modules installed.

    Current mainstream rack systems use 5.12kWh / 51.2V / 100Ah modules, generally with 4–12 modules connected in series for systems between approximately 20kWh and 60kWh.

    The system normally consists of battery modules, a high-voltage battery control unit, BMS, DC protection, communication cables and a rack or cabinet.

    It can be connected to a compatible high-voltage hybrid inverter, PCS or energy storage inverter.

    Main Features


    High-Voltage Battery Architecture

    Multiple battery modules are connected in series to increase the DC voltage while maintaining the same amp-hour capacity.

    Typical configurations provide:

    204.8VDC-614.4VDC nominal system voltage

    with system operating voltage approximately:

    166.4VDC-700VDC

    depending on the selected configuration.

    Deye's current BOS-G system uses 4–12 modules for 20.48–61.44kWh systems, with nominal voltages from 204.8V to 614.4V.

    5.12kWh Modular Battery Design

    A typical battery module provides:

    51.2V / 100Ah / 5.12kWh

    This modular design allows different system capacities to be created by adjusting the number of battery modules.

    Current Deye BOS-G Pro and Dyness HV51100 modules use this same 51.2V / 100Ah / 5.12kWh format.

    Lithium Iron Phosphate Technology

    The system uses LiFePO4 / LFP battery chemistry, providing:

    • High thermal stability
    • Long cycle life
    • Stable charge and discharge performance
    • Good safety characteristics
    • Low maintenance
    • No memory effect
    • Suitability for frequent energy cycling

    Integrated Battery Management System

    The system is equipped with an intelligent Battery Management System.

    Depending on configuration, BMS functions may include:

    • Cell voltage monitoring
    • Module voltage monitoring
    • System voltage monitoring
    • Charge current monitoring
    • Discharge current monitoring
    • Cell temperature monitoring
    • State of Charge (SoC)
    • State of Health (SoH), where supported
    • Cell balancing
    • Overvoltage protection
    • Undervoltage protection
    • Overcurrent protection
    • Short-circuit protection
    • Over-temperature protection
    • Low-temperature protection
    • Communication fault monitoring
    • Alarm and shutdown functions

    High-Voltage Control Unit

    A high-voltage battery cluster normally includes a dedicated:

    Battery Distribution Unit / Battery Control Unit / High-Voltage Box

    depending on system design.

    The control unit manages high-voltage output, system communication and electrical protection between the battery rack and compatible PCS or inverter.

    Deye's current BOS-G Pro uses a dedicated high-voltage battery cluster control box rated for 200–1000VDC.

    Modular Capacity Expansion

    Typical configurations include:

    20.48kWh / 25.60kWh / 30.72kWh / 35.84kWh / 40.96kWh / 46.08kWh / 51.20kWh / 56.32kWh / 61.44kWh

    System capacity is adjusted by changing the number of series-connected battery modules.

    Long Cycle Life

    Selected high-voltage rack-mounted LFP battery systems provide:

    6,000+ cycles

    under specified testing conditions.

    Deye BOS-G specifies 36,000 cycles at 25±2°C, 0.5C charge/discharge and 70% end-of-life capacity; Dyness HV51100 also specifies more than 6,000 cycles under its stated conditions.

    High Depth of Discharge

    Recommended Depth of Discharge is typically:

    90%–95%, depending on battery model and warranty conditions

    Deye BOS-G specifies 90% recommended DoD, while Dyness HV51100 cycle-life testing is stated at 95% DoD.

    CAN and RS485 Communication

    Depending on the selected configuration, communication interfaces can include:

    CAN / CAN2.0 / RS485

    These interfaces allow communication between the BMS and compatible high-voltage inverter or PCS.

    Rack-Mounted Installation

    Battery modules are designed for installation inside a battery rack or cabinet.

    Selected systems use a 19-inch rack-mounted structure, making module arrangement, cable management and maintenance more convenient. Deye describes BOS-G as a standard rack-mounted modular high-voltage battery architecture.

    Technical Specifications


    Parameter

    Specification

    Product Type

    High-Voltage Rack-Mounted LiFePO4 Battery System

    Battery Chemistry

    Lithium Iron Phosphate (LiFePO4 / LFP)

    Typical System Energy

    Approx. 20.48kWh–61.44kWh

    Battery Module Energy

    Typically 5.12kWh

    Battery Module Voltage

    Typically 51.2V

    Battery Module Capacity

    Typically 100Ah

    Battery Modules in Series

    Typically 4–12 Units

    Nominal System Voltage

    Approx. 204.8VDC–614.4VDC

    System Operating Voltage

    Approx. 166.4VDC–700VDC, Model Dependent

    Usable Energy

    Typically Approx. 90%–95% of Nominal Energy, Model Dependent

    Recommended Charge Current

    Typically Approx. 50A

    Recommended Discharge Current

    Typically Approx. 50A

    Maximum Continuous Current

    Up to Approx. 100A on Selected Models

    Peak Discharge Current

    Up to Approx. 125A for Short Duration on Selected Models

    Rated DC Power

    Model Dependent; Up to Approx. 20.48kW–61.44kW on Applicable Architectures

    Recommended Depth of Discharge

    Approx. 90%–95%, Model Dependent

    Cycle Life

    ≥6,000 Cycles on Selected Models under Specified Conditions

    Battery Management System

    Integrated BMS

    High-Voltage Control Unit

    BDU / Battery Control Unit / High-Voltage Box

    Communication

    CAN / CAN2.0 / RS485

    Cell Balancing

    Supported

    Status Monitoring

    SoC / Voltage / Current / Temperature / Alarm Status

    Installation

    Rack-Mounted / Cabinet-Mounted

    Rack Type

    19-Inch Standard Rack on Applicable Models

    Protection Rating

    Typically IP20

    Charging Temperature

    Typically 0°C to 55°C

    Discharging Temperature

    Typically -20°C to 55°C

    Storage Temperature

    Typically 0°C to 35°C

    Relative Humidity

    Typically 5%–95%, Model Dependent

    Installation Altitude

    Typically Up to Approx. 2,000m without Derating on Applicable Models

    Cooling Method

    Natural / Passive Cooling, Model Dependent

    Compatible Equipment

    High-Voltage Hybrid Inverter / PCS / Energy Storage Inverter

    Application

    Residential / Small Commercial / Off-Grid / Backup / Solar Energy Storage

    Warranty

    According to Selected Model and Warranty Conditions

    The current BOS-G specification lists 50A recommended current, 100A nominal current and 125A peak discharge current, while operating temperature is 0–55°C for charging and -20–55°C for discharge.

    Typical Capacity Configurations


    Battery Modules

    Nominal Energy

    Nominal Voltage

    Typical Operating Voltage

    4 Modules

    20.48kWh

    204.8V

    166.4–233.6V

    5 Modules

    25.60kWh

    256.0V

    208–292V

    6 Modules

    30.72kWh

    307.2V

    249.6–350.4V

    7 Modules

    35.84kWh

    358.4V

    291.2–408.8V

    8 Modules

    40.96kWh

    409.6V

    332.8–467.2V

    9 Modules

    46.08kWh

    460.8V

    374.4–525.6V

    10 Modules

    51.20kWh

    512.0V

    416–584V

    11 Modules

    56.32kWh

    563.2V

    457.6–642.4V

    12 Modules

    61.44kWh

    614.4V

    499.2–700V

    These representative values correspond to the current Deye BOS-G architecture using 51.2V / 5.12kWh modules.

    Typical Usable Energy


    For a system configured around approximately 90% DoD, representative usable energy is:

    Nominal Energy

    Approx. Usable Energy

    20.48kWh

    18.43kWh

    25.60kWh

    23.04kWh

    30.72kWh

    27.64kWh

    35.84kWh

    32.25kWh

    40.96kWh

    36.86kWh

    46.08kWh

    41.47kWh

    51.20kWh

    46.08kWh

    56.32kWh

    50.68kWh

    61.44kWh

    55.29kWh

    Actual usable energy depends on BMS settings, inverter settings, DoD, temperature and system configuration. Deye publishes the same usable-energy values for its BOS-G series based on its specified test conditions.

    Typical Battery Module Parameters


    A representative 5.12kWh high-voltage rack battery module can have:

    Parameter

    Typical Specification

    Battery Chemistry

    LiFePO4

    Nominal Energy

    5.12kWh

    Nominal Voltage

    51.2V

    Rated Capacity

    100Ah

    Typical Dimensions

    Approx. 440–481mm W × 535–585mm D × 133–140mm H

    Typical Weight

    Approx. 43.5–46kg

    Communication

    CAN / System Communication via Control Unit

    Protection Rating

    Typically IP20

    Current Deye BOS-G Pro modules are approximately 440×585×133mm and 46kg, while Dyness HV51100 modules are approximately 481×535×140mm and 43.5kg.

    Working Principle

    Solar PV modules generate DC electricity, which is converted and managed by a compatible high-voltage hybrid inverter or PCS.

    When photovoltaic generation exceeds the instantaneous load demand, excess electricity can be used to charge the high-voltage battery system.

    When photovoltaic generation is insufficient, at night, or during a grid outage in a compatible backup system, stored battery energy is discharged through the inverter or PCS to supply electrical loads.

    Battery modules are connected in series to increase system voltage.

    The BMS and high-voltage control unit continuously monitor battery voltage, current, temperature and operating status.

    c55e101c-4b59-43b0-a1a8-c5cda9

    Typical System Configuration


    A typical system can consist of:

    **Solar PV Modules

    • High-Voltage Hybrid Inverter / PCS
    • High-Voltage Battery Control Unit
    • Rack-Mounted LiFePO4 Battery Modules
    • Battery Rack / Cabinet
    • DC Protection
    • CAN / RS485 Communication
    • AC Distribution
    • Utility Grid
    • Electrical Loads**

    Applications


    This high-voltage rack-mounted battery system is suitable for:

    • Large residential solar storage
    • Villas
    • Small commercial buildings
    • Offices
    • Shops
    • Farms
    • Workshops
    • Small factories
    • Off-grid solar systems
    • Backup power systems
    • Microgrids
    • Solar + Storage projects
    • Areas with unstable utility grids

    Deye specifically positions its BOS-G system for applications such as supermarkets, banks, schools, farms and small factories.

    High-Voltage Rack Battery vs. 51.2V Low-Voltage Rack Battery


    The two products should not be confused.

    51.2V Low-Voltage Rack Battery

    Battery modules are normally connected in parallel.

    Parallel connection increases:

    Ah capacity and kWh energy

    while nominal voltage remains approximately:

    51.2V

    High-Voltage Rack Battery System

    Battery modules are primarily connected in series.

    Series connection increases:

    system voltage and total energy

    For example:

    4 × 51.2V modules = 204.8V

    8 × 51.2V modules = 409.6V

    12 × 51.2V modules = 614.4V

    This high-voltage architecture is intended for compatible high-voltage inverters or PCS.

    Monitoring & Communication


    Depending on the battery, inverter and monitoring configuration, users may monitor:

    • State of Charge
    • Battery voltage
    • Battery current
    • Charge power
    • Discharge power
    • Battery temperature
    • Charging status
    • Discharging status
    • BMS alarms
    • Protection status
    • Historical operating data

    Compatible Inverter Requirements


    Before quotation or system configuration, the following inverter parameters should be confirmed:

    • Inverter brand and model
    • High-voltage battery input range
    • Maximum battery charge current
    • Maximum battery discharge current
    • Battery communication protocol
    • CAN / RS485 compatibility
    • Minimum and maximum number of battery modules
    • Inverter firmware version
    • Maximum supported battery energy
    • Approved battery compatibility list

    Battery voltage alone is not sufficient to confirm compatibility.

    Environmental Requirements


    Rack-mounted battery modules are commonly intended for protected indoor installation.

    Typical IP20 battery modules should be protected from:

    • Rain
    • Direct water exposure
    • Excessive moisture
    • Conductive dust
    • Extreme ambient temperatures

    Installation requirements must follow the selected battery model's technical manual.

    Safety & Protection


    Depending on configuration, the battery system may provide:

    • Cell overvoltage protection
    • Cell undervoltage protection
    • Module overvoltage protection
    • Module undervoltage protection
    • Charge overcurrent protection
    • Discharge overcurrent protection
    • Short-circuit protection
    • Over-temperature protection
    • Low-temperature charging protection
    • Cell balancing
    • Insulation monitoring on selected systems
    • Communication fault protection
    • System alarm
    • Emergency shutdown
    • DC high-voltage isolation

    Some systems also incorporate additional rack-level fire-protection functions. Deye describes aerosol fire extinguishing in its BOS-G rack system architecture.

    Monitoring & Communication


    Depending on the selected BMS and inverter, the system can monitor:

    • State of Charge
    • State of Health
    • Battery voltage
    • Battery current
    • Charge power
    • Discharge power
    • Cell voltage
    • Battery temperature
    • Alarm status
    • Protection status
    • Communication status
    • Historical operating data

    Communication interfaces typically include:

    CAN / CAN2.0 / RS485

    Installation Requirements


    Before installation, confirm:

    • Correct rack dimensions
    • Rack load-bearing capacity
    • Battery module quantity
    • High-voltage control-unit position
    • DC cable routing
    • Communication cable routing
    • Grounding
    • Ventilation
    • Required installation clearances
    • Inverter voltage compatibility
    • Battery polarity
    • Emergency isolation requirements

    Because each 5.12kWh module typically weighs approximately 44–46kg, the complete rack can weigh several hundred kilograms depending on system capacity.

    Environmental Requirements


    These rack-mounted systems are generally designed for indoor installation.

    Typical enclosure protection is:

    IP20

    Representative operating conditions include:

    Charging: 0°C to 55°C
    Discharging: -20°C to 55°C
    Storage: approximately 0°C to 35°C

    If outdoor installation is required, the battery rack should be installed inside a suitable outdoor-rated enclosure or battery room designed for the environmental conditions.

    Compliance, Safety & Transport Documentation


    Depending on the selected model and destination market, applicable certificates or documentation can include:

    • IEC 62619
    • CE
    • EMC
    • UL 1973
    • UL 9540A
    • UN38.3
    • SDS
    • VDE Requirements
    • Other Regional Requirements

    Deye's BOS-G documentation lists combinations including CE, IEC 62619, UL1973, UL9540A and UN38.3 depending on version and target market, while Dyness HV51100 documentation lists CE/EMC and UN38.3.

    Actual certification must be confirmed according to the specific supplied model.

    UN38.3 is lithium-battery transport testing/documentation. SDS is safety documentation and should not be described simply as a product certification.

    Information Required for Quotation


    For accurate configuration and quotation, please provide:

    1. Required battery capacity
    2. Required backup duration
    3. Inverter or PCS brand and model
    4. Inverter battery voltage range
    5. Maximum charge/discharge current
    6. Solar PV system capacity
    7. Daily electricity consumption
    8. Maximum load power
    9. Required battery module quantity
    10. Required rack or cabinet configuration
    11. Installation location
    12. Ambient temperature
    13. Destination country
    14. Required certifications
    15. Required communication protocol

    Packing & Shipping


    Battery modules and high-voltage control equipment are packed separately or inside the battery rack depending on shipment requirements and system design.

    Lithium battery transportation may require:

    UN38.3 Test Documentation
    SDS
    Dangerous Goods Declaration
    Battery Transport Documentation
    Specialized Export Packaging

    Battery racks and modules should be protected against impact, moisture, incorrect stacking and terminal short circuit during transportation.

    Chudu Metal

    Solar PV Modules, Solar Mounting Components & Solar Product Supplier from China
    🌐 Website:  www.chudufastener.com
    📧 Email:  han@hbchudu.com
    📱 WhatsApp / Phone: +86 19333039217

    description2

    Contact Us

    Our experts will solve them in no time.